各种换气次数汇总
本文来源:网络
序号 | 系统类型 | 正常 | 事故 | 出处 |
---|---|---|---|---|
1 |
燃油锅炉房(首层) |
不小于 3 |
不小于 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
||
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
||
|
|
|
||
|
|
|
||
|
|
|
||
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
1、厨房和卫生间全面通风换气次数不宜小于 3 次//h;
1、制冷机房的通风应符合下列规定:
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1、可能突然放散大量有害气体或有爆炸危险气体的场所应设置事故通风。事故通风量宜根据放散物的种类、安全及卫生浓度要求,按全面排风计算确定,且换气次数不应小于 12 次//h;
2、事故通风应根据放散物的种类,设置相应的检测报警及控制系统。事故通风的手动控制装置应在室内外便于操作的地点分别设置;
8.10. 3 氨制冷机房设计应符合下列规定:
1、氨制冷机房单独设置且远离建筑群;
2、机房内严禁采用明火供暖;
3、机房应有良好的通风条件,同时应设置事故排风装置,换气次数每小时不少于 12 次,排风机应选用防爆型;
1、机房内严禁采用明火采暖;
2、设置事故排风装置,换气次数每小时不小于12次,排风机选用防爆型。
6.5.8 空气调节区的换气次数,应符合下列规定:
1、舒适性空气调节每小时不宜小于5次,但高大空间的换气次数应按其次负荷通过计算确定;
2、工艺性空气调节不宜小于表6.5.8所列的数值。
表6.5.8 工艺性空气调节换气次数
|
|
|
|
|
|
|
|
|
|
|
|
15.3.7 设在其它建筑物内的燃油、燃气锅炉房的锅炉间,应设置独立的送排风系统,其通风装置应防爆,新风量必须符合下列要求:
1、锅炉房设置在首层时,对采用燃油作燃料的,其正常换气次数每小时不应小于3次,事故换气次数每小时不应小于3次;对于燃气作燃料的,其正常换气次数每小时不应小于6次,事故换气次数每小时不应小于12次;
2、锅炉房设置在半地下或半地下室时,其正常换气次数每小时不应小于6次,事故换气次数每小时不应小于12次;
3、锅炉房设置在地下或地下室时,其换气次数每小时不应小于12次;
4、送入锅炉房的新风总量,必须大于锅炉房3次的换气量;
5、送入控制室的新风量,应按最大班操作人员计算。
注:换气量不包括锅炉燃烧所需的空气量。