洁净室霉菌污染,有哪些来源?
Normally, the maximum humidity in a pharmaceutical clean room is supposed to lie below 70% to prevent the formation of moulds.
通常,制药洁净室的最大湿度应为70%以下以避免霉菌产生。
In the GMP measuring point list, the humidity sensor is usually defined with an alert limit at 60% and an action limit at 70%.
对于GMP监测点,湿度探头通常设置警戒限为60%,行动限为70%。
A real risk of formation of moulds only exists if elevated humidity values occur over a longer period of time. Different values for this can be found in literature, like more than three hours a day with a surface humidity of 60-100% (in German language), for example.
只有长时间相对湿度较高才有形成霉菌的风险。这可以在文献中找到,如每天超过3小时表面湿度达到60%-100%。
According to DIN report 4108-8 (prevention of mould growth in residential buildings), mould formation occurs if the relative humidity of a surface reaches a value of more than 80% for at least twelve hours a day on at least five consecutive days.
根据DIN报告4108-8(住房预防霉菌生长),如果表面的相对湿度每天至少有12小时超过80%并持续5天,将会生长霉菌。
洁净室中常见的霉菌来源如下:
长期维护不当的洗衣机,在内胆外围及腔室内长满霉菌,往洗衣机中加入强效消毒剂并不能杀灭霉菌。
空调系统操作不当继而引起凝露,例如,热的空气遇到冷的设备表面
来自物料,例如在长途运输或在库房存放过程中包装打湿继而滋生霉菌
开裂的地板或墙面
其他易于滋生霉菌的环境示例如下:
维护不当的洗衣间及其相邻的理衣间
换鞋间,由于通风不当或清洁消毒不当
维护不当的器具清洗间及洁具清洗间
洁具存放间,例如洁具未能及时干燥继而成为一个污染源
需要频繁用水的房间,例如包衣液配制间、配浆间等
设备上的设计死角,例如某些设计不当的球阀、管道、不易于清洁的区域
维护不当的地漏及设备不恰当的与排水口直通,例如没有空气隔断
洁净室内潜在的卫生死角,例如设备底部、顶部、灯座等
来自物料,例如物料本身易于滋生霉菌,如某些营养性原辅料及某些不卫生的设备润滑油
物料频繁进出的区域
人员频繁进出的区域
易于产生湿气的区域,例如用于培养基灭菌的湿热灭菌设备周围
来自洁净室上方夹层的漏水,例如夹层中的纯化水管道漏水
通风不良的场所,例如换气次数仅为1的房间
维护不当的水池及水池下方的排水设施
木质工具
液体废弃物未及时清理出车间
未经过滤的空气流入
公众号
GMP办公室
专业的GMP合规性研究组织
国内外(FDA、EMA、MHRA、CFDA、WHO、PIC/S等)GMP法规解读;
国内外制药行业GMP监管动态;
GMP技术指南(ISPE、PDA、ISO、ASTM等)分享